Skip to main content
Siemens 3RV1021-1JA15-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1JA15-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV1021-1JA15-ZW96

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1JA15-ZW96, 10 A continuous rated current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, screw-type terminals, 45 x 97 x 96 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1021-1JA15-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-1JA15-ZW96 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV1021-1JA15-ZW96 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1021-1JA15-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1021-1JA15-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1021-1JA15-ZW96 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1021-1JA15-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1021-1JA15-ZW96 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker for DIN-rail panels

Breaking capacity and fault clearing

This breaker delivers 100 kA breaking capacity at both 240 V and 400 V AC, dropping to 42 kA at 500 V and 6 kA at 690 V. The phase failure detection built into the SIRIUS design adds a layer of protection for three-phase motors running on supply legs that may drop one phase.

Screw-type terminals on the main current circuit accept solid conductors: 2x (0.5 … 1.5 mm²) and 2x (0.75 … 2.5 mm²). Stranded conductors: 2x (1 … 2.5 mm²) and 2x (2.5 … 6 mm²). The auxiliary switch is transverse design with its own terminal set. The IP20 rating on the front means the breaker is touch-safe for panel interiors but not suitable for washdown environments.

Shock resistance is rated at 25g / 11 ms, which covers most industrial vibration environments. The mechanical endurance of the main contacts is typically 100 000 operations, and the maximum switching frequency in AC-3 duty is 15 operations per hour.

Frequently asked questions

What is the breaking capacity of 3RV1021-1JA15-ZW96 at 400 V?

100 kA at 400 V AC, which is the standard industrial distribution voltage for most panels.

What trip class does this motor protection circuit breaker have?

CLASS 10, meaning it trips within 10 seconds at 7.2× rated current, matching standard induction motor startup characteristics.

What wire sizes does the screw terminal accept?

Solid: 2x (0.5 … 1.5 mm²) and 2x (0.75 … 2.5 mm²). Stranded: 2x (1 … 2.5 mm²) and 2x (2.5 … 6 mm²).

Where can I buy 3RV1021-1JA15-ZW96 and get current pricing?

This part is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ.

MPN