Skip to main content
Siemens 3RV1021-1JA15-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1JA15-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV1021-1JA15-ZW97

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1JA15-ZW97, 10 A continuous rated current, 4 kW at 400 V, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1021-1JA15-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1021-1JA15-ZW97 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W

Protection & Tripping

3RV1021-1JA15-ZW97 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1021-1JA15-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1021-1JA15-ZW97 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1021-1JA15-ZW97 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany

Environmental

3RV1021-1JA15-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1021-1JA15-ZW97 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker — 10 A, CLASS 10, 100 kA

The Siemens SIRIUS 3RV1021-1JA15-ZW97 is a motor protection circuit breaker rated for 10 A continuous current and 4 kW at 400 V AC. It's built for protecting three-phase induction motors up to that load, with CLASS 10 trip characteristics — meaning it will trip within 10 seconds at 7.2× rated current, fast enough to protect standard motors during locked-rotor conditions without nuisance tripping on startup. Breaking capacity is 100 kA at 240 V and 400 V AC, dropping to 42 kA at 500 V and 6 kA at 690 V. That 100 kA figure at 400 V is high for this class — it handles high-fault utility feeds without needing an upstream current-limiting fuse in most panel designs. Phase failure detection is built in, so if one phase drops on the line side, the breaker trips — critical for preventing single-phasing damage on delta-connected motor loads. No ground fault detection on this unit, so that's a separate device if needed.

Mounting and panel fit

Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 50022. At 45 mm wide, it takes a single 9 mm module width on the rail. Depth is 96 mm, height 97 mm — standard SIRIUS footprint, so it drops into existing Siemens motor starter assemblies or standalone DIN-rail enclosures without panel rework. Mounting position is any orientation, and the front face carries IP20 finger-safe protection — fine for enclosed panels, not for washdown zones.

Termination and aux contacts

Main circuit terminals are screw-type, accepting solid conductors 2× (0.5 to 1.5 mm²) and 2× (0.75 to 2.5 mm²), or stranded 2× (1 to 2.5 mm²) and 2× (2.5 to 6 mm²). That covers most motor power wiring up to 4 mm² — typical for a 10 A motor circuit. An auxiliary switch is included, rated 1 A at 24 V, 0.5 A at 230 V, 0.15 A at 60 V. The auxiliary switch design is transverse. No additional auxiliary contact blocks are fitted (: 0 for auxiliary contacts).

Frequently asked questions

Where can I buy 3RV1021-1JA15-ZW97 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time, no stock or price figures published here.

What is the breaking capacity of 3RV1021-1JA15-ZW97 at 400 V?

100 kA at 400 V AC. Also rated 100 kA at 240 V, 42 kA at 500 V, and 6 kA at 690 V AC.

What is the trip class of this motor protection circuit breaker?

CLASS 10 — trips within 10 seconds at 7.2× rated current, suitable for standard induction motor protection.

Does 3RV1021-1JA15-ZW97 include phase failure detection?

Yes, phase failure detection is built in. No ground fault detection on this unit.

MPN
3RV1021-1JA15-ZW97