Siemens 3RV1021-1KA10-ZW98 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1KA10-ZW98 SIRIUS Motor Protection Circuit B

MPN3RV1021-1KA10-ZW98

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1KA10-ZW98, 12.5 A continuous, CLASS 10, 100 kA breaking capacity at 400 V, screw terminals, IP20 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1021-1KA10-ZW98 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1021-1KA10-ZW98 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W

Protection & Tripping

3RV1021-1KA10-ZW98 — Protection & Tripping
ParameterValue
Overload release setting range9 ... 12.5 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1021-1KA10-ZW98 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1021-1KA10-ZW98 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)

Mechanical

3RV1021-1KA10-ZW98 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1021-1KA10-ZW98 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1021-1KA10-ZW98 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

What the ratings mean for fit

The Siemens 3RV1021-1KA10-ZW98 is a SIRIUS motor protection circuit breaker rated for 12.5 A continuous current with a CLASS 10 trip characteristic — meaning it clears overloads fast enough to protect a motor winding during a locked-rotor event without nuisance tripping on startup inrush. The 100 kA breaking capacity at 400 V AC means it safely interrupts fault currents up to that level without cascading upstream; at 690 V the breaking capacity drops to 6 kA, so verify the available fault current at the installation point. Phase failure detection is built in, which protects three-phase motors from single-phasing damage.

Mounting and integration

Snap-on mounting onto 35 mm DIN rail per DIN EN 50022 — no tools needed for rail attachment, but screw-type terminals for both main and auxiliary/control circuits require a screwdriver for wiring. Accepts solid or stranded conductors: 2x (1... 2.5 mm²) and 2x (2.5... 6 mm²) per terminal. Zero clearance needed at the back or sides, so it packs tight in a dense panel. IP20 on the front means finger-safe but not washdown-rated.

Frequently asked questions

Where can I buy 3RV1021-1KA10-ZW98?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of 3RV1021-1KA10-ZW98 at 400 V?

100 kA at 400 V AC. At 690 V it drops to 6 kA.

What wire sizes does 3RV1021-1KA10-ZW98 accept?

Screw terminals accept solid or stranded: 2x (1... 2.5 mm²) and 2x (2.5... 6 mm²) per terminal. AWG equivalent: 2x (14... 10).

Does 3RV1021-1KA10-ZW98 fit a panel designed for 3RV6021-4DA10?

Footprint differs — the 3RV1021-1KA10-ZW98 is a 45 mm wide SIRIUS 3RV1 frame; the 3RV6021-4DA10 is a different frame size. Verify DIN rail space and terminal layout before swapping without rewiring.

MPN
3RV1021-1KA10-ZW98