Skip to main content
Siemens 3RV1031-4AA10-0BA0 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1031-4AA10-0BA0 SIRIUS Motor Protection Circuit B

MPN3RV1031-4AA10-0BA0

Siemens SIRIUS 3RV1031-4AA10-0BA0, motor protection circuit breaker, 16 A, Trip Class 10, screw terminals, 55 x 140 x 149 mm, IP20 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1031-4AA10-0BA0 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1031-4AA10-0BA0 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)14.5 W
Power loss, per pole (AC, hot)4.8 W
3RV1031-4AA10-0BA0 — Protection & Tripping
ParameterValue
Overload release setting range11 ... 16 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)12 kA
Breaking capacity at 690 V (AC)5 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1031-4AA10-0BA0 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1031-4AA10-0BA0 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.75 ... 16 mm²), 0.75 ... 25 mm²
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 2)
3RV1031-4AA10-0BA0 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1031-4AA10-0BA0 — Environmental
ParameterValue
Operating temperature-50 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1031-4AA10-0BA0 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The 55 mm width takes one slot; depth is 149 mm, so check your gland plate clearance if the panel is shallow. Any mounting position is allowed, and the IP20 front means it's fine inside a closed cabinet but not for a washdown zone. Solid conductors up to 2x 16 mm² or stranded up to 2x 25 mm² (with a single up to 35 mm²) — that covers most motor feeder cables up to the 16 A rating. The box terminals give a solid clamp for high-vibration environments like a conveyor drive.

Protection features and ratings

No ground-fault detection on this unit; that's a separate module if your circuit needs it. Breaking capacity varies with line voltage: 100 kA at 240 V AC, 50 kA at 400 V AC, 12 kA at 500 V AC, and 5 kA at 690 V AC. The 6 kV surge voltage resistance (impulse withstand) covers the standard transient environment in an industrial panel. Power dissipation is 14.5 W total in hot operating state, or 4.8 W per pole. That's moderate — you won't need forced cooling in a typical enclosure, but don't pack it tight against heat-sensitive components.

MPN
3RV1031-4AA10-0BA0