Siemens 3RV1031-4EA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1031-4EA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV1031-4EA10-ZX95

Siemens SIRIUS 3RV1031-4EA10-ZX95 motor protection circuit breaker, 32 A continuous, 15 kW at 400 V, Class 10, screw terminals, 55 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1031-4EA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1031-4EA10-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)19 W
Power loss, per pole (AC, hot)6.3 W
3RV1031-4EA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range22 ... 32 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)4 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1031-4EA10-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1031-4EA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.75 ... 16 mm²), 0.75 ... 25 mm²
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 2)
3RV1031-4EA10-ZX95 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1031-4EA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1031-4EA10-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Snap-on mounting onto 35 mm DIN rail per DIN EN 50022. 55 mm wide, 140 mm tall, 149 mm deep. Zero clearance required at the back or sides — no extra breathing gap needed for the enclosure cutout. Screw-type box terminals on the main circuit accept 2x (0.75…16 mm²) solid or 2x (0.75…25 mm²) stranded; auxiliary and control circuit uses separate screw terminals.

Rated short-circuit breaking capacity: 100 kA at 240 V AC, 50 kA at 400 V AC, 10 kA at 500 V AC, 4 kA at 690 V AC. Surge voltage resistance rated at 6 000 V.

Power dissipation

19 W total power dissipation in hot operating state; 6.3 W per pole. That matters for thermal rise inside a sealed enclosure — plan the cabinet cooling budget accordingly if you're stacking several breakers in a row.

Frequently asked questions

Will 3RV1031-4EA10-ZX95 drop into a panel specified around 3RV6021-4DA10 without rewiring?

Both are 55 mm wide SIRIUS breakers on the same DIN rail footprint, so the mechanical fit is the same. But the 3RV1031-4EA10-ZX95 uses screw-type box terminals — check whether the existing panel wiring matches the terminal capacity (2x 0.75…16 mm² solid, 2x 0.75…25 mm² stranded).