Skip to main content
Siemens 3RV1031-4EA15-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1031-4EA15-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV1031-4EA15-ZW96

Siemens SIRIUS 3RV1031-4EA15-ZW96, motor protection circuit breaker, 32 A continuous current, CLASS 10 trip class, 50 kA breaking capacity at 400 V AC, screw terminals, IP20 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1031-4EA15-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1031-4EA15-ZW96 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)19 W
Power loss, per pole (AC, hot)6.3 W
3RV1031-4EA15-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range22 ... 32 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)4 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1031-4EA15-ZW96 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1031-4EA15-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 2)
3RV1031-4EA15-ZW96 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1031-4EA15-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1031-4EA15-ZW96 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1031-4EA15-ZW96 is a SIRIUS motor protection circuit breaker rated for 32 A continuous current and 15 kW at 400 V AC (AC-3). Breaking capacity is 100 kA at 240 V AC, 50 kA at 400 V AC, 10 kA at 500 V AC, and 4 kA at 690 V AC. That 50 kA at 400 V covers most industrial panel fault-current levels up to a 2000 kVA transformer secondary. The auxiliary switch is transverse design, rated 1 A at 24 V, 0.5 A at 230 V, 0.15 A at 60 V — sufficient for signaling to a PLC input or contactor coil, but watch the DC derating if driving an inductive load. Power dissipation in hot operating state is 19 W. Operating frequency is limited to 15 switching cycles per hour at AC-3 duty; this is a motor-protection device, not a high-cycle contactor.

Any mounting position is allowed. Backwards and side clearances are 0 mm — no air gap needed, which simplifies panel layout when stacking breakers side by side. Dimensions are 55 mm wide × 140 mm high × 149 mm deep. Main circuit terminals accept solid wire 2×(0.5–1.5 mm²) and 2×(0.75–2.5 mm²), stranded wire 2×(0.75–25 mm²) and 1×(0.75–35 mm²), or AWG 2×(18–2) and 1×(18–2). That 35 mm² stranded capacity on a single conductor is generous for a 32 A breaker — useful for long cable runs where voltage drop drives larger gauge.

Shock resistance is 25 g for 11 ms. RoHS compliance date is July 1, 2006 — the part is RoHS-compliant for EU markets. Lifecycle stage is marked as current production. This is an active catalog item, not a phase-out or obsolete line.

Frequently asked questions

What is the breaking capacity of 3RV1031-4EA15-ZW96 at 400 V AC?

50 kA at 400 V AC.

Where can I buy 3RV1031-4EA15-ZW96?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What wire sizes does 3RV1031-4EA15-ZW96 accept?

Main circuit terminals accept solid 2×(0.5–1.5 mm²) and 2×(0.75–2.5 mm²), stranded 2×(0.75–25 mm²) and 1×(0.75–35 mm²), or AWG 2×(18–2) and 1×(18–2).

Does 3RV1031-4EA15-ZW96 include phase failure protection?

Yes, phase failure detection is built in. Ground fault detection is not included.

MPN
3RV1031-4EA15-ZW96