Siemens 3RV1031-4EA15-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1031-4EA15-ZX95 SIRIUS MCCB, 32 A, 15 kW, CLASS 1

MPN3RV1031-4EA15-ZX95

Siemens SIRIUS 3RV1031-4EA15-ZX95 motor-protective circuit breaker, 32 A, 15 kW at 400 V, CLASS 10, screw terminals, 55 x 140 x 149 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1031-4EA15-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1031-4EA15-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)19 W
Power loss, per pole (AC, hot)6.3 W
3RV1031-4EA15-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range22 ... 32 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)4 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1031-4EA15-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1031-4EA15-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 2)
3RV1031-4EA15-ZX95 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1031-4EA15-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1031-4EA15-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

SIRIUS 3RV1031-4EA15-ZX95 — motor-protective circuit breaker, 32 A, CLASS 10

The Siemens 3RV1031-4EA15-ZX95 is a SIRIUS motor-protective circuit breaker rated for 32 A continuous current and 15 kW at 400 V AC-3. Breaking capacity is 100 kA at 240 V AC, 50 kA at 400 V AC, 10 kA at 500 V AC, and 4 kA at 690 V AC.

Mounting and integration — DIN rail, any position

Shock rated to 25g / 11 ms, so it holds up on mobile equipment or near rotating machinery. Main circuit terminals are screw-type box terminals accepting solid 2x (0.5…1.5 mm²) and 2x (0.75…2.5 mm²), or stranded 2x (0.75…25 mm²) and 1x (0.75…35 mm²). Auxiliary and control circuit terminals are also screw-type. The auxiliary switch is a transverse design and is field-installable as a product extension.

Front-face protection class IP20. RoHS compliance date 07/01/2006. Power dissipation in hot operating state is 19 W.

Frequently asked questions

What is the depth of 3RV1031-4EA15-ZX95?

The depth is 149 mm. Combined with 55 mm width and 140 mm height, it fits standard DIN-rail panel layouts with zero clearance required at back or sides.

MPN
3RV1031-4EA15-ZX95