Skip to main content
Siemens 3RV1041-4JA15-ZW95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1041-4JA15-ZW95 SIRIUS Motor Protection Circuit B

MPN3RV1041-4JA15-ZW95

Siemens SIRIUS 3RV1041-4JA15-ZW95 motor protection circuit breaker, 63 A rated continuous current, CLASS 10 trip class, 50 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1041-4JA15-ZW95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1041-4JA15-ZW95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)34 W
Power loss, per pole (AC, hot)11.3 W
3RV1041-4JA15-ZW95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)12 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1041-4JA15-ZW95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h
3RV1041-4JA15-ZW95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1041-4JA15-ZW95 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth174 mm
Mounting positionany
3RV1041-4JA15-ZW95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1041-4JA15-ZW95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1041-4JA15-ZW95 is a SIRIUS motor protection circuit breaker rated for 63 A continuous current, sized for a 30 kW motor at 400 V AC with CLASS 10 trip characteristics — meaning it disconnects within 10 seconds at 7.2× rated current, protecting against overload and short-circuit on motor start-up. The IP20 front face keeps fingers out of live terminals. At 240 V it's 100 kA, at 500 V it drops to 12 kA, and at 690 V it's 6 kA.

The 63 A continuous rating and 30 kW motor capacity at 400 V tell you this is a heavy motor feeder — think 50–75 hp pump or compressor on 480 V three-phase. The CLASS 10 trip curve is standard for standard induction motors; it lets through starting inrush without nuisance tripping. No ground-fault detection on this unit — that's a separate add-on or upstream GFCI. Operating temperature spans -20 to +60 °C, storage -50 to +80 °C. The 25g / 11 ms shock rating means it holds calibration on a machine tool or conveyor line that sees vibration.

Main circuit terminals are screw-type with box terminals. Solid conductors: 2× (0.5…1.5 mm²) and 2× (0.75…2.5 mm²). Stranded: 2× (10…50 mm²) or 1× (10…70 mm²). That's enough for 63 A on a 16–25 mm² stranded cable, depending on local code. Auxiliary switch is transverse design, rated 1 A at 24 V, 0.5 A at 230 V, 0.15 A at 60 V — enough for a PLC digital input or contactor coil feedback.

Frequently asked questions

How do I get pricing and availability for 3RV1041-4JA15-ZW95?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number.

What is the closest functional second-source to 3RV1041-4JA15-ZW95?

The 3RV2021-4NA25 is a similar SIRIUS motor protection breaker but check the continuous current rating and trip class — this 3RV1041-4JA15-ZW95 is a 63 A CLASS 10 unit, so verify the peer's ratings match your motor load before substituting.

What is the depth of 3RV1041-4JA15-ZW95?

Listed depth is 174 mm — fits standard 200 mm deep enclosures with room for wiring.

What solid conductor sizes does 3RV1041-4JA15-ZW95 accept?

Solid conductors: 2× (0.5…1.5 mm²) and 2× (0.75…2.5 mm²).

Will 3RV1041-4JA15-ZW95 drop into a panel specified for 3RV2021-4NA25 without rewiring?

Both mount on 35 mm DIN rail, but the 3RV1041-4JA15-ZW95 is 70 mm wide — verify the peer's width and terminal layout. Terminal sizes differ (solid 0.5–2.5 mm² vs stranded 10–70 mm² on this unit), so check conductor fit before assuming a drop-in swap.

What compliance documentation does Siemens provide for 3RV1041-4JA15-ZW95?

As a SIRIUS product from Siemens, it carries CE marking for the European market and is designed to IEC/EN 60947 standards for motor protection. RoHS and REACH declarations are standard Siemens documentation available on request.

MPN