It trips in CLASS 10 (under 10 seconds at locked rotor), so it clears a stalled motor fast enough to keep the windings from cooking — that's the main reason you'd pick this over a slower thermal breaker.
The 3RV1041-4MA15 delivers 100 kA breaking capacity at 240 V AC, 50 kA at 400 V AC, 8 kA at 500 V AC, and 5 kA at 690 V AC.
Installation notes
Zero clearance required at the sides or rear — the 70 mm width and 165 mm height fit a standard DIN-rail footprint. Any mounting position works; no derating for orientation. Shock rated to 25g for 11 ms, so it holds up in mobile or vibrating equipment.