Siemens 3RV1042-4HB10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1042-4HB10 SIRIUS Motor Protection Circuit Breake

MPN3RV1042-4HB10

Siemens SIRIUS 3RV1042-4HB10, motor protection circuit breaker, 50 A, CLASS 20, 100 kA breaking capacity at 400 V AC, screw terminals, IP20 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1042-4HB10 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1042-4HB10 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)27 W
Power loss, per pole (AC, hot)9 W
3RV1042-4HB10 — Protection & Tripping
ParameterValue
Overload release setting range36 ... 50 A
Trip classCLASS 20
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)15 kA
Breaking capacity at 690 V (AC)10 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1042-4HB10 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1042-4HB10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (2.5 ... 35 mm²), 2.5 ... 50 mm²
Conductor range, AWG (main contacts)2x (10 ... 1), 1x (10 ... 2)
3RV1042-4HB10 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth174 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1042-4HB10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1042-4HB10 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Its CLASS 20 trip curve means it allows up to 20 seconds of locked-rotor current before tripping — standard for general-purpose induction motors driving pumps, fans, and conveyors where the start-up transient isn't extreme. Breaking capacity is 100 kA at both 240 V and 400 V AC, dropping to 15 kA at 500 V and 10 kA at 690 V. No ground-fault detection on this variant — if you need that, you're looking at a different 3RV family member.

Zero clearance required at the back or sides — you can butt it against adjacent devices without derating. Any mounting position works, which simplifies layout in tight enclosures. Dimensions are 70 mm wide, 165 mm tall, 174 mm deep. Main circuit terminals accept solid conductors 2x (2.5 to 16 mm²) or stranded 2x (10 to 50 mm²) and 1x (10 to 70 mm²). That's generous lug capacity for a 50 A breaker — no adapter blocks needed for the heavier feeds.

RoHS compliance date is July 1, 2006, meaning it meets the original EU RoHS directive. REACH and other regional compliance documentation is available from the manufacturer.

Frequently asked questions

Does 3RV1042-4HB10 detect phase failure?

Yes, phase failure detection is built in. It does not include ground-fault detection.

What wire sizes does the 3RV1042-4HB10 accept?

Main circuit screw terminals accept solid 2x (2.5 to 16 mm²) and stranded 2x (10 to 50 mm²) or 1x (10 to 70 mm²). AWG equivalents are 2x (10 to 1) and 1x (10 to 2).

MPN