SIRIUS 3RV1321-1BC10 — motor-protective circuit breaker for starter combinations
Rated 2 A continuous and 0.75 kW at 400 V AC-3, it handles small motor loads (pumps, fans, conveyors) in a 45 mm wide package that snaps onto 35 mm DIN rail per EN 50022.
The 100 000 mechanical cycles typical on the main contacts match the duty life of a contactor in the same starter combination.
Termination and panel fit
Solid and stranded conductors: 2x (1 … 2.5 mm²) or 2x (2.5 … 6 mm²) per clamp. AWG equivalents for main contacts: 2x (14 … 10). Mounting position any, zero clearance needed at the sides or rear — 45 mm wide, 97 mm tall, 96 mm deep. IP20 finger-safe on the front; store or ship between -50 and +80 °C, operate between -20 and +60 °C. Shock rated 25g / 11 ms.