Siemens 3RV1321-1DH10-ZX95 SIRIUS Circuit Breaker, 3.2 A, 50

MPN3RV1321-1DH10-ZX95

Siemens SIRIUS 3RV1321-1DH10-ZX95, circuit breaker for starter combinations, 3-pole, 3.2 A continuous, 50 kA breaking at 400 V AC, screw terminals, IP20 front, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1321-1DH10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1321-1DH10-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)3.5 W
Power loss, per pole (AC, hot)1.2 W
3RV1321-1DH10-ZX95 — Protection & Tripping
ParameterValue
Breaking capacity at 240 V (AC)50 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)50 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionNo
Ground-fault detectionNo
3RV1321-1DH10-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1321-1DH10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
3RV1321-1DH10-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1321-1DH10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1321-1DH10-ZX95 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

It's a 3-pole unit rated for 3.2 A continuous current, with a breaking capacity of 50 kA at 400 V AC. That 50 kA holds at 240 V and 500 V too, dropping to 6 kA at 690 V. For motor duty, it's rated 1.1 kW at 400 V in AC-3 service, good for about 15 operations per hour maximum. The main contacts are good for 100,000 mechanical cycles typical.

No clearance needed at the side or backwards. Mounting position is any, which helps in tight enclosures. Main circuit connections are screw-type terminals, accepting 2x (1 to 2.5 mm²) solid or stranded, or 2x (2.5 to 6 mm²). AWG equivalent for the main contacts is 2x (14 to 10). The front face is IP20 rated — finger-safe but not sealed.

Environmental and electrical margins

Rated for altitudes up to 2,000 m. Shock resistance tested at 25g for 11 ms.

Frequently asked questions

Will 3RV1321-1DH10-ZX95 drop into a panel specified around 3RV6011-0CA10?

Both mount on 35 mm DIN rail per EN 50022 with the same footprint, so mechanical fit is the same. However, ratings differ — verify continuous current and breaking capacity match your application before substituting.

MPN