Skip to main content
Siemens 3RV1321-1JC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1321-1JC10 SIRIUS Circuit Breaker, 10 A, 100 kA a

MPN3RV1321-1JC10

Siemens SIRIUS circuit breaker for starter combinations, 3RV1321-1JC10, 10 A continuous, 100 kA breaking capacity at 400 V AC, 3-pole, screw terminals, IP20, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1321-1JC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1321-1JC10 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV1321-1JC10 — Protection & Tripping
ParameterValue
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1321-1JC10 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1321-1JC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1321-1JC10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1321-1JC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1321-1JC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

SIRIUS 3RV1321-1JC10 — Motor Circuit Breaker for Starter Combinations

The Siemens SIRIUS 3RV1321-1JC10 is a 3-pole circuit breaker designed specifically for starter combinations, rated 10 A continuous current and 4 kW at 400 V AC-3 duty. It provides motor and short-circuit protection in a single device, sized for a 45 mm wide DIN-rail footprint. Breaking capacity reaches 100 kA at 400 V AC, dropping to 42 kA at 500 V and 6 kA at 690 V — sufficient for high-fault panels where upstream coordination keeps let-through within the device's rating. The front face carries IP20 finger-safe touch protection.

The 6 kV rated surge voltage resistance (impulse withstand) matches standard industrial distribution panels and supports coordination with upstream surge arrestors.

RoHS compliance dated 01.05.2012. No ground-fault or phase-failure detection built in — those functions require an add-on module or a separate monitoring relay.

Dimensions: 96 mm depth, 45 mm width, 97 mm height — fits standard 45 mm slot spacing. No clearance required at the back or sides for heat dissipation, though the 9.25 W total power loss (3.1 W per pole) should be considered in sealed enclosures. Screw terminals accept 2x (1…2.5 mm²) or 2x (2.5…6 mm²) solid or stranded wire, with ferruled fine-stranded also supported. AWG equivalents: 2x (14…10). The auxiliary switch option (product extension) allows adding a signal contact for remote status.

Frequently asked questions

What is the breaking capacity of 3RV1321-1JC10 at different voltages?

At 240 V AC it is 100 kA, at 400 V AC it is 100 kA, at 500 V AC it is 42 kA, and at 690 V AC it is 6 kA.

What wire sizes does 3RV1321-1JC10 accept?

Screw terminals accept 2x (1…2.5 mm²) or 2x (2.5…6 mm²) solid, stranded, or fine-stranded with ferrule. AWG equivalents are 2x (14…10).

Where can I buy 3RV1321-1JC10 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Does 3RV1321-1JC10 include ground-fault or phase-failure detection?

No. Ground-fault detection and phase-failure detection are not built in. Those functions require an add-on module or a separate monitoring relay.

MPN
3RV1321-1JC10