Siemens 3RV1321-1KC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1321-1KC10 SIRIUS Circuit Breaker, 12.5 A, 5.5 kW

MPN3RV1321-1KC10

Siemens SIRIUS circuit breaker, 3RV1321-1KC10, for starter combinations, 3-pole, 12.5 A rated continuous current, 5.5 kW motor rating at 400 V AC, 100 kA breaking capacity at 400 V AC, screw-type terminals, DIN rail snap-on mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1321-1KC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1321-1KC10 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV1321-1KC10 — Protection & Tripping
ParameterValue
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionNo
Ground-fault detectionNo
3RV1321-1KC10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1321-1KC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
3RV1321-1KC10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1321-1KC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1321-1KC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

The Siemens 3RV1321-1KC10 is a SIRIUS circuit breaker designed specifically for starter combinations — motor-starting duty where the breaker provides both overload and short-circuit protection in a single device. Rated 12.5 A continuous current, it handles motor loads up to 5.5 kW at 400 V AC, with a 100 kA breaking capacity at that voltage. That 100 kA SCCR means it can safely interrupt a bolted fault on a high-capacity distribution bus without upstream fuses needing to clear — a real advantage in panel designs where coordination is tight.

Mounting and integration

Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 50022. The 45 mm width and 97 mm height fit standard enclosure rail spacing; 96 mm depth leaves clearance for wiring behind the panel door. Any mounting position is allowed, so orientation in a crowded cabinet isn't a constraint. Main circuit connections are screw-type terminals accepting solid or stranded conductors: 2x (1 to 2.5 mm²) or 2x (2.5 to 6 mm²) per pole. AWG equivalents are 2x (14 to 10). The front face carries an IP20 rating — safe for finger-probe access in a closed panel, but not for washdown environments.

Breaking capacity across voltage

Breaking capacity varies with line voltage: 100 kA at 240 V and 400 V AC, derating to 42 kA at 500 V AC, and 6 kA at 690 V AC. At 690 V the fault-current capability drops sharply — verify your available fault current at that voltage before specifying. The rated impulse withstand voltage is 6 kV, with a rated insulation voltage of 690 V.

MPN