It's rated 16 A continuous, which translates to 7.5 kW at 400 V in AC-3 duty (the standard motor-switching curve). The interrupting ratings tell the real story: 100 kA at 240 V AC, 50 kA at 400 V AC, 12 kA at 500 V AC, and 5 kA at 690 V AC. For a panel on a 400 V system with a transformer feeding a motor control center, that 50 kA SCCR gives you headroom to coordinate with upstream breakers without cascading faults. If your plant runs at 690 V, you're still covered at 5 kA — enough for most industrial distribution.
Zero clearance needed at the back or sides (0 mm backwards, 0 mm at the side), so you can pack it tight in a panel — no extra breathing room required. Screw-type terminals for both main and auxiliary circuits; the main terminals accept solid 2x (0.75…16 mm²) or stranded 2x (0.75…25 mm²) with a single conductor up to 35 mm². That's plenty of lug for a 16 A device. No ground-fault or phase-failure detection built in — this is a straight motor-protective breaker, not a multifunction monitor.
