The 50 kA breaking capacity at 400 V is the figure that governs SCCR for the branch circuit; at 240 V it rises to 100 kA, and at 690 V it drops to 6 kA — so verify the available fault current at your installation voltage.
The 70 mm width and 165 mm height fit a standard MCC bucket or small enclosure; depth is 174 mm, so allow clearance for the box terminals and wiring. Any mounting position is permitted — no derating for horizontal or vertical orientation.
Main circuit terminals accept solid conductors 2x (2.5 … 16 mm²) and stranded 2x (10 … 50 mm²) or 1x (10 … 70 mm²). AWG equivalents: 2x (10 … 1) solid, 1x (10 … 2) stranded. Auxiliary and control circuit terminals are screw-type as well. The box-terminal design on the main circuit provides a secure connection for larger cable sizes typical of a 50 A motor branch.
Shock resistance 25g / 11 ms. RoHS compliance date (substance prohibition) 07/01/2006. Surge voltage resistance rated 6 000 V. The part carries finger-safe touch protection against electrical shock.