Motor circuit breaker for starter combinations
The 690 V rated voltage covers 480/575 V installations.
Dimensions: 70 mm wide, 165 mm high, 174 mm deep — zero clearance needed at sides or rear, so it packs tight in a panel. Any mounting position. Finger-safe touch protection and IP20 on the front keep live parts covered during maintenance.
Breaking capacity and environmental limits
Breaking capacity drops with voltage: 100 kA at 240 V and 400 V, 30 kA at 500 V, 12 kA at 690 V. Shock rated 25g / 11 ms. Power dissipation 21 W hot, 7 W per pole.
Listed as current production. RoHS compliance date 07/01/2006. No ground-fault or phase-failure detection built in. Auxiliary switch extension possible. Operating frequency max 15 operations per hour at AC-3.