Skip to main content
Siemens 3RV1353-6EP10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1353-6EP10 SIRIUS MCCB, 4 A, 85 kA at 400 V

MPN3RV1353-6EP10

Siemens SIRIUS molded-case circuit breaker, 3RV1353-6EP10, 4 A, 85 kA at 400 V AC, 3-pole, screw terminals, for starter combinations.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1353-6EP10 — Identification
ParameterValue
SeriesSIRIUS
Product designationmolded-case circuit breaker
3RV1353-6EP10 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)8 000 V
Number of poles3
3RV1353-6EP10 — Protection & Tripping
ParameterValue
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)85 kA
Breaking capacity at 500 V (AC)50 kA
Breaking capacity at 690 V (AC)10 kA
Phase-failure detectionNo
Ground-fault detectionNo
3RV1353-6EP10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)25 000
Switching frequency, AC-3 (max.)15 1/h
3RV1353-6EP10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
3RV1353-6EP10 — Mechanical
ParameterValue
Height130 mm
Width90 mm
Depth70 mm
Mounting positionany
3RV1353-6EP10 — Environmental
ParameterValue
Operating temperature-25 ... +70 °C
Storage temperature-40 ... +70 °C
Transport temperature-40 ... +70 °C
3RV1353-6EP10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

Rated at 4 A continuous current with a magnetic overcurrent release set to a non-adjustable 13 x In, this 3-pole unit delivers 85 kA breaking capacity at 400 V AC, which is the figure that governs its SCCR in a 400 V panel.

The 85 kA at 400 V is the headline number for this MCCB, but the full SCCR curve matters for selectivity studies: 100 kA at 240 V, 85 kA at 400 V, 50 kA at 500 V, and 10 kA at 690 V. At 690 V the breaker still clears 10 kA, which is relevant for 690 V industrial networks common in mining or marine installations. The 1.5 kW motor rating at 400 V (AC-3) gives a quick sizing rule: this breaker pairs with a 1.5 kW, 400 V three-phase motor in a standard DOL starter.

Physical integration

Mounts via screw fixing (not DIN rail) in any position. Dimensions: 130 mm high, 90 mm wide, 70 mm deep — fits standard 90 mm wide MCCB slots in motor control centers. Zero clearance required at the sides and rear for heat dissipation, which simplifies panel layout.

Frequently asked questions

Where can I buy 3RV1353-6EP10 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the breaking capacity of 3RV1353-6EP10 at 400 V?

85 kA at 400 V AC. The full SCCR curve: 100 kA at 240 V, 85 kA at 400 V, 50 kA at 500 V, and 10 kA at 690 V.

What are the mounting dimensions of 3RV1353-6EP10?

130 mm high, 90 mm wide, 70 mm deep. Screw fixing, any mounting position, zero clearance at sides and rear.

MPN
3RV1353-6EP10