Skip to main content
Siemens 3RV1421-0AA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1421-0AA10 SIRIUS Circuit Breaker, 0.16 A, Class

MPN3RV1421-0AA10

Siemens SIRIUS circuit breaker for transformer protection, 3-pole, 0.16 A rated continuous current, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw terminals, IP20 front, DIN-rail snap-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1421-0AA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1421-0AA10 — Electrical
ParameterValue
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1421-0AA10 — Protection & Tripping
ParameterValue
Overload release setting range0.11 ... 0.16 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1421-0AA10 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1421-0AA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1421-0AA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1421-0AA10 — Environmental
ParameterValue
Max. installation altitude2 000 m
3RV1421-0AA10 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

The Siemens 3RV1421-0AA10 is a SIRIUS circuit breaker specifically designed for transformer protection — a 3-pole device rated at 0.16 A continuous current with Trip Class 10, meaning it can handle the inrush of a small transformer without nuisance tripping while still providing short-circuit and overload protection downstream. Its breaking capacity is a flat 100 kA across the full voltage range from 240 V to 690 V AC — that means the same SCCR rating holds regardless of whether the panel is fed from a 400 V or 690 V supply, simplifying coordination studies. The device includes phase failure detection, so if one phase drops out on a three-phase transformer, the breaker trips — preventing single-phasing damage to the load.

The 0 mm backward clearance requirement means the breaker can be mounted flush against the back panel. Screw terminals on both the main and auxiliary circuits accept solid or stranded conductors: 2x 1–2.5 mm² or 2x 2.5–6 mm² per terminal, with AWG equivalents 2x 14–10. The front is IP20 and finger-safe, so it can be installed on a live busbar in a closed panel without additional shrouding.

The substance prohibition date of 01.05.2012 aligns with RoHS and REACH compliance timelines for this class. Surge voltage withstand is rated at 6 kV, and shock resistance at 25g for 11 ms — suitable for industrial environments with moderate vibration.

Frequently asked questions

How do I get pricing and availability for 3RV1421-0AA10?

Submit an RFQ through the storefront; the part is sourced to order through independent distribution, and current pricing and stock levels are confirmed at quote time.

What are the key specifications of 3RV1421-0AA10?

Rated continuous current is 0.16 A, Trip Class 10, 3-pole, breaking capacity 100 kA at 240–690 V AC, operating temperature -20 to +60 °C, IP20 front, DIN-rail mount.

MPN