Skip to main content
Siemens 3RV1421-0BA10-ZI41 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1421-0BA10-ZI41 SIRIUS Circuit Breaker, 0.2 A, Cl

MPN3RV1421-0BA10-ZI41

Siemens SIRIUS circuit breaker for transformer protection, 3RV1421-0BA10-ZI41, 0.2 A continuous current, Trip Class 10, 100 kA breaking capacity at 400 V AC, 3-pole, screw terminals, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1421-0BA10-ZI41 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1421-0BA10-ZI41 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1421-0BA10-ZI41 — Protection & Tripping
ParameterValue
Overload release setting range0.14 ... 0.2 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1421-0BA10-ZI41 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1421-0BA10-ZI41 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1421-0BA10-ZI41 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1421-0BA10-ZI41 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1421-0BA10-ZI41 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

SIRIUS transformer-protection circuit breaker, 0.2 A, Class 10

The Siemens SIRIUS 3RV1421-0BA10-ZI41 is a 3-pole circuit breaker designed specifically for transformer protection, rated at 0.2 A continuous current with Trip Class 10 thermal-magnetic release. It delivers 100 kA breaking capacity across the full voltage range from 240 V through 690 V AC, meaning it can safely interrupt fault currents up to that level without cascading upstream — critical for coordinating with downstream transformer inrush and upstream feeder protection.

The 45 mm width and 96 mm depth fit a standard 45 mm-wide DIN slot — one module width — leaving adjacent slots free for auxiliary contact blocks or other SIRIUS components. Screw-type terminals on both main and auxiliary circuits accept 2x (1... 2.5 mm²) solid or stranded, or 2x (2.5... 6 mm²) for heavier tails. Finger-safe IP20 front protection means the busbars and terminals are touch-safe once installed in an enclosure.

Frequently asked questions

Where can I buy 3RV1421-0BA10-ZI41?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this circuit breaker?

100 kA at 240 V, 400 V, 500 V, and 690 V AC — the same high interrupting rating across the full voltage range, simplifying coordination studies.

Does 3RV1421-0BA10-ZI41 detect phase failure?

Yes, phase failure detection is included. The breaker will trip if any phase is lost, protecting the transformer from single-phasing.

What is the Trip Class of this breaker?

Trip Class 10, meaning it must trip within 10 seconds at 7.2× the current setting — suitable for protecting transformers against sustained overloads while allowing for inrush.

MPN