Breaking capacity is a flat 100 kA across the board — 240 V, 400 V, 500 V, and 690 V AC — so it handles high-fault-current scenarios without cascading upstream.
The 45 mm width and 96 mm depth mean it fits standard panel layouts — no extra clearance needed behind the rail. Any mounting position works, and it's rated for 25g / 11 ms shock — fine for most industrial machinery and conveyors.
Wiring and thermal considerations
Terminals accept solid or stranded wire: 2x (1 to 2.5 mm²) and 2x (2.5 to 6 mm²) per clamp, or 2x (14 to 10 AWG). Finely stranded with ferrule is also supported. Power dissipation runs 7.25 W total in hot operating state, or 2.4 W per pole — factor that into your panel's thermal budget, especially in a crowded DIN rail.