Zero clearance needed at the back or sides, so you can pack breakers tight on the rail without derating. Front face carries IP20 protection — finger-safe for a panel environment, but not for washdown. Screw-type terminals on the main circuit accept solid wire 2x (0.5…1.5 mm²) or 2x (0.75…2.5 mm²), and stranded 2x (1…2.5 mm²) or 2x (2.5…6 mm²). Any mounting position works.
Auxiliary switch and ratings
The breaker includes a transverse auxiliary switch rated at 1 A at 24 V, 0.5 A at 230 V, and 0.15 A at 60 V. That covers typical PLC input or contactor coil signaling. The auxiliary contacts are separate from the main circuit — zero auxiliary contacts on the main switch means the auxiliary is a built-in add-on, not a separate block. Mechanical life of the main contacts is 100,000 operations typical.
Environmental limits
Shock rated at 25 g for 11 ms.