Transformer-protection MCCB with Class 10 trip
The 3.2 A continuous current rating sets the maximum load the breaker can carry indefinitely without tripping — match this to the transformer's full-load amperage. Power dissipation is 7.25 W total, or 2.4 W per pole — factor this into panel thermal calculations to avoid derating.
Mounting and wiring integration
Accepts solid or stranded conductors: 2x 1–2.5 mm² and 2x 2.5–6 mm² per terminal, or AWG 14–10. The 45 mm width occupies one standard modular slot. Clearance: 0 mm backwards and 0 mm at the side — can be mounted flush against adjacent devices. Any mounting position is permitted.
Shock resistance is 25g for 11 ms. Surge voltage resistance rated at 6000 V. Touch protection is finger-safe. RoHS compliance date is 01.05.2012. The front panel is IP20.