Breaking capacity and voltage ratings
Rated for 690 V AC, this breaker delivers 100 kA breaking capacity at 240 V, 400 V, and 500 V AC, dropping to 8 kA at 690 V AC — the derating at the top end is typical for this class and means the 690 V application needs a fault-current study to confirm the 8 kA covers the prospective short-circuit.
Protection features and environmental limits
Shock resistance rated at 25g for 11 ms, suitable for industrial machinery with moderate vibration.
Listed as current production (active lifecycle stage).