Accepts solid or stranded conductors: 2x (1 … 2.5 mm²) or 2x (2.5 … 6 mm²) per terminal.
Electrical and environmental ratings
Shock rated at 25g for 11 ms. Mounting position any orientation. Surge voltage resistance 6 kV. Maximum switching frequency under AC-3 duty is 15 operations per hour — fine for transformer primary switching, not for frequent motor starting.
Compliance documentation
RoHS compliance date listed as May 1, 2012 — the part meets RoHS and REACH substance restrictions as of that date. No UL or CSA listing appears in the spec record; the primary approvals are IEC/EN based. For a project requiring UL recognition, request the manufacturer's declaration or check the specific variant suffix.