Skip to main content
Siemens 3RV1421-1GA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1421-1GA10-ZX95 SIRIUS Circuit Breaker, 6.3 A, Cl

MPN3RV1421-1GA10-ZX95

Siemens SIRIUS circuit breaker for transformer protection, 3RV1421-1GA10-ZX95, 6.3 A continuous, Trip Class 10, 100 kA breaking capacity at 400 V AC, 690 V rated, screw terminals, snap-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1421-1GA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1421-1GA10-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1421-1GA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range4.5 ... 6.3 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1421-1GA10-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1421-1GA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1421-1GA10-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1421-1GA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1421-1GA10-ZX95 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

Transformer-protection circuit breaker, 6.3 A, Class 10

Finger-safe touch protection (IP20 on the front) meets panel safety requirements.

The 6.3 A continuous rating sets the maximum steady load the breaker carries without tripping. Power dissipation is 7.25 W total in hot operating state (2.4 W per pole). That heat must be considered in enclosure sizing, especially when multiple breakers are ganged in a small panel. Maximum operating frequency is 15 cycles per hour in AC-3 duty — not a high-cycling device; it is sized for occasional switching, not repetitive motor starting.

Panel integration

The 45 mm width occupies one standard module slot. Screw terminals accept 2x (1...2.5 mm²) or 2x (2.5...6 mm²) solid or stranded — strip length and ferrule size per the terminal spec. Auxiliary switch option (product extension available) fits the same footprint. Shock rated at 25g for 11 ms; vibration resistance not listed but the DIN-rail clip holds under typical industrial panel conditions. Backwards and side clearances are 0 mm — can be mounted flush against adjacent devices.

Frequently asked questions

How do I get current pricing and availability for 3RV1421-1GA10-ZX95?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution.

What is the breaking capacity of 3RV1421-1GA10-ZX95 at 400 V?

100 kA at 400 V AC, and the same at 240 V and 500 V. At 690 V it drops to 6 kA.

What compliance documentation does this breaker carry?

RoHS compliance date is 01.05.2012. The product is a Siemens SIRIUS circuit breaker; full IEC/UL documentation is available from the manufacturer.

MPN
3RV1421-1GA10-ZX95