Siemens 3RV1421-4AA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1421-4AA10 SIRIUS Circuit Breaker, 16 A, Transfor

MPN3RV1421-4AA10

Siemens SIRIUS circuit breaker, 3RV1421-4AA10, for transformer protection, 16 A rated, CLASS 10 trip, 50 kA breaking capacity at 400 V AC, screw terminals, 45 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1421-4AA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1421-4AA10 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV1421-4AA10 — Protection & Tripping
ParameterValue
Overload release setting range11 ... 16 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)4 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1421-4AA10 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1421-4AA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
3RV1421-4AA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Mounting positionany
3RV1421-4AA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1421-4AA10 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

What it is and what it does

The Siemens 3RV1421-4AA10 is a SIRIUS circuit breaker designed specifically for transformer protection — not a general-purpose motor-protective breaker, but one tuned for the inrush and overload profile of a transformer primary. It carries a continuous current rating of 16 A and a rated insulation voltage of 690 V. The CLASS 10 trip characteristic means it will open within 10 seconds at 7.2× rated current, which is fast enough to protect a transformer winding from sustained overload without nuisance-tripping on magnetizing inrush.

Mounting and wiring

Snaps onto 35 mm DIN rail per DIN EN 50022 — screw and snap-on, so it stays put under vibration. The 45 mm width eats one standard module slot. Screw-type terminals on both main and auxiliary circuits; accepts solid or stranded wire up to 6 mm², with two conductors per clamp. No backwards clearance needed, so you can butt it against the left side of the enclosure. Mount in any position.

Protection and diagnostics

Phase failure detection is built in — if one phase drops out, the breaker trips. No ground-fault detection, so that needs a separate module if required. The front is IP20 finger-safe. Surge voltage resistance is 6 kV. Power dissipation runs 9.25 W total, 3.1 W per pole.

Frequently asked questions

What is the closest functional alternative to 3RV1421-4AA10?

The 3RV6021-4DA10 is a functional peer in the same SIRIUS family, but verify the trip class and breaking capacity against your transformer's inrush profile — the 3RV1421-4AA10 is specifically designed for transformer protection and may have a different trip curve than a general-purpose motor-protective breaker.

What compliance documentation does Siemens provide for 3RV1421-4AA10?

RoHS compliance is confirmed with a substance prohibition date of May 1, 2012. Standard Siemens documentation includes a CE declaration and manufacturer's declaration for the EU low-voltage directive. For UL or IEC certifications, request the specific declaration from your Siemens contact or distributor.