Transformer-protection circuit breaker, 16 A, Class 10
The 45 mm width occupies a single modular unit on the rail. Terminal capacity accepts 2x (1…2.5 mm²) solid or stranded, and 2x (2.5…6 mm²) for larger feeds. Zero clearance required at the back or sides — the breaker can be stacked directly against adjacent devices without derating.
Breaking capacity varies by system voltage: 100 kA at 240 V AC, 50 kA at 400 V AC, 10 kA at 500 V AC, and 4 kA at 690 V AC. At 690 V the 4 kA figure limits application to lower-fault installations or requires upstream current-limiting fuses for full coordination.
Listed as current production. RoHS compliance effective 01.05.2012. The IP20 finger-safe front protection meets touch-protection requirements for enclosed panel mounting. Shock resistance 25g / 11 ms suitable for machinery-mounted applications.