Breaking capacity is 100 kA at 240 V AC, 50 kA at 400 V AC, 12 kA at 500 V AC, and 5 kA at 690 V AC — so on a 400 V supply it clears a 50 kA prospective fault without upstream fuses needing to coordinate.
Main circuit terminals accept solid 2x (0.75…16 mm²) or stranded 2x (0.75…25 mm²) with a single conductor up to 35 mm² — enough for the 20 A feed without a separate terminal block.
For a BOM line that needs a transformer-protection breaker at 20 A, Class 10, with 50 kA breaking at 400 V, the 3RV1431-4BA10 is the current-production choice — no need to stockpile or search surplus.