It carries a 100 kA breaking capacity at 400 V — the same rating holds at 240 V, 500 V, and 690 V, so it clears faults across the common industrial voltage bands without derating the interrupting rating.
The size S00 footprint — 45 mm wide, 90 mm high, 75 mm deep — fits the compact slot common in SIRIUS modular panels. Clearance requirements: 20 mm upwards and downwards, 9 mm at the side, zero forwards and backwards. Screw-type terminals for the main current circuit accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²).
The rated operational voltage spans 20 to 690 V. The maximum switching frequency in AC-3 and AC-3e duty is 15 operations per hour.