Skip to main content
Siemens 3RV2011-0AA20 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-0AA20 SIRIUS Motor Protection Circuit Breake

MPN3RV2011-0AA20
Active

Siemens SIRIUS 3RV2011-0AA20 motor protection circuit breaker, size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-0AA20 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2011-0AA20 — Electrical
ParameterValue
Rated operational current (Ie)0.16 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV2011-0AA20 — Protection & Tripping
ParameterValue
Overload release setting range0.11 ... 0.16 A
Instantaneous short-circuit trip current2.1 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2011-0AA20 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2011-0AA20 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (20 ... 12)

Mechanical

3RV2011-0AA20 — Mechanical
ParameterValue
Height106 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2011-0AA20 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2011-0AA20 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens 3RV2011-0AA20 is a SIRIUS motor protection circuit breaker, size S00, designed to protect motors against overload and short-circuit. Its Trip Class 10 ensures fast tripping under locked-rotor conditions — within 10 seconds at 7.2× rated current — which is the standard for standard-duty induction motors driving pumps, fans, and compressors. The 100 kA breaking capacity at 400 V AC means it can safely interrupt fault currents up to that level without upstream fuses or a larger breaker, simplifying coordination in a distribution panel.

Mounting and integration

Mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715. The 45 mm width (three 17.5 mm modules) fits standard enclosure cutouts, and the 97 mm depth leaves clearance for wiring behind the rail. Spring-loaded terminals on the main circuit accept 2× (0.5 … 4 mm²) solid or stranded — no lug crimping needed, which speeds panel wiring.

Lifecycle and sourcing

The lifecycle stage is listed as current, meaning Siemens still manufactures this order code. No successor has been announced. For a BOM line that calls out 3RV2011-0AA20, this part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Frequently asked questions

Where can I buy 3RV2011-0AA20 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Will 3RV2011-0AA20 drop into a panel specified for 3RV2011-0AA10 without rewiring?

Yes, both are size S00 breakers with the same 45 mm width and screw/snap-on DIN rail mounting, so the mechanical fit is identical. The terminal type and wiring capacity are the same (spring-loaded, 2× 0.5–4 mm²). The difference is in the trip setting range — verify the overload setting matches your motor FLA before swapping.

What is the breaking capacity of 3RV2011-0AA20 at 400 V?

100 kA at 400 V AC, which is the same at 240 V, 500 V, and 690 V AC — a flat 100 kA across the common industrial voltages.

MPN
3RV2011-0AA20