Siemens 3RV2011-0CA25-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-0CA25-ZX95 SIRIUS Motor Protection CB, 0.25

MPN3RV2011-0CA25-ZX95
Active

Siemens SIRIUS motor protection circuit breaker, size S00, 0.25 A, CLASS 10, 100 kA breaking capacity at 400 V AC, spring-type terminals, 1 NO + 1 NC auxiliary contacts.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-0CA25-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker

Electrical

3RV2011-0CA25-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)0.25 A
Rated voltage20 ... 690 V

Protection & Tripping

3RV2011-0CA25-ZX95 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current3.3 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA

Specifications

3RV2011-0CA25-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Other specifications

3RV2011-0CA25-ZX95 — Other specifications
ParameterValue
At 400 V rated value100 kA
At 500 V rated value100 kA
Substance prohibitance10/01/2009

Product details

Motor protection breaker, 0.25 A, CLASS 10, spring terminals

The Siemens SIRIUS 3RV2011-0CA25-ZX95 is a motor protection circuit breaker in size S00, designed for three-phase motor branch circuits. Its thermal overload release is adjustable from 0.18 to 0.25 A, and the magnetic short-circuit release trips instantaneously at 3.3 A. The CLASS 10 trip class means it will disconnect within 10 seconds at 7.2× the set current — fast enough to protect standard IEC induction motors during a locked-rotor event without nuisance tripping on normal starts. Breaking capacity is a flat 100 kA across the full voltage range: 240 V, 400 V, 500 V, and 690 V AC. That SCCR (short-circuit current rating) lets you coordinate downstream contactors and overloads without adding a separate fuse or upstream breaker, provided the available fault current stays under 100 kA at the panel. Termination is spring-type (cage clamp) on the main circuit, accepting 2× (0.5 to 4 mm²) solid or stranded. The unit includes factory-fitted transverse auxiliary contacts: 1 NO + 1 NC, rated for 100,000 mechanical/electrical operations. Snap-on mounting onto 35 mm DIN rail per EN 60715, any orientation.

Sourcing and lifecycle

RoHS compliance date is noted as 10/01/2009, meaning the design meets EU Directive 2002/95/EC. No separate UL or CSA listing appears in the spec record, but the SIRIUS range typically carries IEC/EN 60947-2 and 60947-4-1 approvals; verify the specific certification mark on the unit if your panel requires UL 508 listing.

Panel integration and fit

Size S00 footprint: 45 mm wide, 97 mm deep, 106 mm tall (with handle). Snap-on DIN rail mounting, no tools needed. Side-by-side mounting requires 30 mm clearance to adjacent devices for heat dissipation; zero clearance when using the side-by-side arrangement with the same S00 frame. The spring terminals accept ferruled or solid conductors — strip length is 8 mm for the cage clamp. The breaker integrates directly with SIRIUS contactors in sizes S00 and S0 via a screwless bus bar system, forming a compact motor starter assembly. The handle provides a visible break position and can be padlocked in the OFF position for lockout/tagout.

Frequently asked questions

What is the trip class and what does it mean?

The trip class is CLASS 10, meaning the overload relay will trip within 10 seconds at 7.2× the set current. This is the standard class for protecting standard IEC induction motors against locked-rotor conditions.

Will 3RV2011-0CA25-ZX95 drop into a panel wired for 3RV2011-0BA20?

Both are size S00 with the same 45 mm width and 35 mm DIN rail mounting, so the mechanical fit is identical. The key difference is the current range: the -0BA20 adjusts 0.14–0.2 A, while this -0CA25 adjusts 0.18–0.25 A. If your motor FLA falls within 0.18–0.2 A, it is a direct swap; below 0.18 A you need the -0BA20. The spring terminals on this unit are the same type as the -0BA20, so no rewiring of the main circuit is required.

Where can I buy 3RV2011-0CA25-ZX95 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the rated voltage range?

The rated operational voltage is 20 to 690 V AC, covering common three-phase systems from 24 V control circuits up to 690 V industrial mains.