Skip to main content
Siemens 3RV2011-0FA15-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-0FA15-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV2011-0FA15-ZW97
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2011-0FA15-ZW97, Trip Class 10, 100 kA at 400 V, screw terminals, 45 mm width, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-0FA15-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2011-0FA15-ZW97 — Electrical
ParameterValue
Rated operational current (Ie)0.5 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV2011-0FA15-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range0.35 ... 0.5 A
Instantaneous short-circuit trip current6.5 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2011-0FA15-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2011-0FA15-ZW97 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV2011-0FA15-ZW97 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2011-0FA15-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2011-0FA15-ZW97 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

What it is and what it does

The Siemens 3RV2011-0FA15-ZW97 is a SIRIUS motor protection circuit breaker designed for motor protection in industrial control panels. It combines a circuit breaker and overload relay in one device, providing short-circuit and overload protection for motors up to 0.1 kW at 230 V. Trip Class 10 means it will trip within 10 seconds at 7.2× the set current, which is the standard for standard induction motor starting — it lets the motor accelerate without nuisance tripping but clears a stalled rotor fast enough to protect the winding. Rated breaking capacity of 100 kA at 400 V means it can safely interrupt a fault current of that magnitude without welding contacts or cascading failure upstream — sized for high-fault panels where the available short-circuit current is substantial. Built-in phase failure detection protects the motor from single-phasing, which is a common cause of winding burnout on three-phase lines. No ground fault detection — that's handled separately if required.

Mounting and integration

Mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715. Width is 45 mm — a standard 2-module footprint that fits most panel layouts. Depth is 97 mm, which is typical for this class and leaves room for wiring behind the gland plate. Mounting position is any, so it can go sideways or upside-down in tight enclosures without derating. Terminal screws for main contacts are M3, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded copper. Clearance distances: 50 mm upwards and downwards, 30 mm at the sides, 0 mm forwards and backwards — the forward/backward zero means it can be stacked flush against the panel door or backplane, saving space.

Frequently asked questions

What are the key ratings for 3RV2011-0FA15-ZW97?

Trip Class 10, breaking capacity 100 kA at 400 V, phase failure detection, motor protection design for 0.1 kW at 230 V. Width 45 mm, depth 97 mm, DIN rail mount.

Will 3RV2011-0FA15-ZW97 drop into a panel specified around 3RV2011-0AA10?

The 3RV2011-0FA15-ZW97 shares the same 45 mm width and DIN rail mounting as the 3RV2011-0AA10, so it fits the same panel footprint and rail. Terminal sizes and wiring are identical. The difference is in the trip class and breaking capacity — verify the protection settings match your motor.

How do I get pricing and availability for 3RV2011-0FA15-ZW97?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

MPN