Motor protection breaker, Class 10, 100 kA
The 100 kA breaking capacity at 400 V (also rated 100 kA at 240 V, 500 V, and 690 V) gives high fault-current headroom, so it can be used in panels with large upstream transformers without needing a current-limiting fuse ahead of it. The size S00 frame keeps the width at 45 mm, depth at 97 mm, and height at 97 mm — compact enough for dense DIN-rail layouts.
Mounting position is any orientation. Clearance: 50 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards — so it can be packed tightly in a row with no front gap needed. Screw terminals accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². The screwdriver shaft diameter is 5 to 6 mm.