Skip to main content
Siemens 3RV2011-0HA10-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-0HA10-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV2011-0HA10-ZW96
Active

Siemens SIRIUS 3RV2011-0HA10-ZW96, motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 0.55...0.8 A, magnetic short-circuit trip 10 A, screw terminals, 100 kA breaking capacity at 400 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-0HA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker

Electrical

3RV2011-0HA10-ZW96 — Electrical
ParameterValue
Rated operational current (Ie)0.8 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V

Protection & Tripping

3RV2011-0HA10-ZW96 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current10 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA

Endurance & Switching

3RV2011-0HA10-ZW96 — Endurance & Switching
ParameterValue
Switching frequency, AC-3 (max.)15 1/h

Specifications

3RV2011-0HA10-ZW96 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor protection circuit breaker, size S00, 0.8 A, CLASS 10

The Siemens 3RV2011-0HA10-ZW96 is a SIRIUS motor protection circuit breaker in size S00, designed to protect a motor drawing up to 0.8 A full-load current. The adjustable overload release covers 0.55 to 0.8 A, and the instantaneous magnetic short-circuit trip responds at 10 A. CLASS 10 trip class means it will trip within 10 seconds at 7.2× the set current — fast enough to protect a standard induction motor during a locked-rotor event without nuisance tripping on normal start-up. Rated for system voltages from 20 to 690 V AC, this breaker delivers a 100 kA breaking capacity across the 240 V to 690 V range (-). That SCCR rating means it can safely interrupt a fault current up to 100,000 A without welding contacts or rupturing — critical for high-fault installations where upstream breakers are sized above 65 kA. The unit snaps onto a 35 mm DIN rail per DIN EN 60715, fitting standard panel layouts.

Compliance and documentation

The 3RV2011-0HA10-ZW96 carries a RoHS compliance date of 10/01/2009, indicating it meets the EU RoHS directive for restricted substances. The part is designed for motor protection per IEC/EN 60947-2 and 60947-4-1 standards. Standard documentation includes the manufacturer's datasheet and declaration of conformity covering CE, UL, and CSA certifications — these are available on request with the RFQ.

Frequently asked questions

What is 3RV2011-0HA10-ZW96's trip class?

It is CLASS 10, meaning it will trip within 10 seconds at 7.2× the overload setting — suitable for standard motor starting profiles.

What is the breaking capacity of 3RV2011-0HA10-ZW96?

100 kA at 240 V, 400 V, 500 V, and 690 V AC (-). This high SCCR rating allows it to be used in high-fault-capacity installations without requiring upstream fuses for fault protection.

Will 3RV2011-0HA10-ZW96 drop into a panel specified around 3RV1011-0HA10?

The 3RV2011-0HA10-ZW96 and 3RV1011-0HA10 share the same size S00 footprint, 45 mm width, screw-type terminals, and snap-on DIN rail mounting. The key difference is the adjustable overload range: 0.55...0.8 A for the -ZW96 versus 0.55...0.8 A for the 3RV1011-0HA10 — functionally identical for the same motor FLA. The -ZW96 variant is a multi-unit package (24 units per pack). Panel rewiring is not required for a direct swap.

How do I get current pricing and availability for 3RV2011-0HA10-ZW96?

Submit an RFQ through this listing. The part is sourced to order against your BOM line, with current pricing and confirmed lead time provided at quote time.

MPN
3RV2011-0HA10-ZW96