Breaking capacity hits 100 kA at 240 V, 400 V, 500 V, and 690 V AC — that's industrial-grade fault clearance, meaning it can sit upstream of a motor starter without needing a separate fuse for SCCR compliance in most panel builds. The 45 mm width and 97 mm depth fit the S00 footprint; screw terminals accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm² — typical for motor branch circuits up to that cross-section.
Snap-on DIN rail mounting (35 mm per DIN EN 60715) with screw-terminal main contacts (M3). The 45 mm width is one standard module — no special adapter needed. Clearance above and below is 50 mm; side clearance 30 mm. Zero forward or backward clearance means it can sit flush against a back panel or enclosure wall.