Mounting and clearance
Clearance requirements are 50 mm above and below, 30 mm to the side, and zero forward or backward — so it can be stacked tightly in a row with other SIRIUS components. The M3 screw terminals accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²), which covers most motor feeder wiring.
Auxiliary contact ratings: 1 A at 24 V, 0.5 A at 120/125/230 V, and 0.15 A at 60 V — these are typical for signaling the breaker's status to a PLC or indicator lamp. The main circuit is rated for 20 to 690 V, covering most global motor voltages. Mounting position is any, which simplifies panel layout.