Skip to main content
Siemens 3RV2011-0KA10 — Motor Protection Circuit Breakers (MPCB)

Siemens SIRIUS 3RV2011-0KA10 Motor Circuit Breaker, Class 10

MPN3RV2011-0KA10
Active

Siemens SIRIUS 3RV2011-0KA10 motor-protective circuit breaker, Class 10, 45 mm wide, screw terminals, phase failure detection.

$113.73 – $175.04Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2011-0KA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2011-0KA10 — Electrical
ParameterValue
Rated operational current (Ie)1.25 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2011-0KA10 — Protection & Tripping
ParameterValue
Overload release setting range0.9 ... 1.25 A
Instantaneous short-circuit trip current16 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2011-0KA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2011-0KA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2011-0KA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2011-0KA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2011-0KA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV2011-0KA10 is a motor-protective circuit breaker designed for Class 10 trip characteristics, meaning it will trip within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during locked-rotor conditions without nuisance tripping on normal starts.

The interrupting capacity is rated 100 kA at 240 V, 400 V, 500 V, and 690 V AC — that covers high-fault utility feeds common in industrial plants. The screw-type terminals accept up to 2× 4 mm² stranded or solid, which covers most motor branch-circuit wiring up to 16 A.

Frequently asked questions

What are the key dimensions for panel layout?

Width is 45 mm, depth is 97 mm, height is 97 mm. It mounts on 35 mm DIN rail with screw or snap-on fastening, and requires 50 mm clearance above and below, 30 mm to the side, and zero forward or backward clearance.

Does this breaker detect phase failure?

Yes, phase failure detection is included, so the breaker will trip if one phase is lost, protecting the motor from single-phasing damage.

MPN