It carries a 100 kA short-circuit breaking capacity at 400 V AC, 500 V AC, and 690 V AC — meaning it safely interrupts faults up to that level without cascading upstream, a key spec for panel SCCR compliance per IEC 60947-2 and UL 508A.
The 100 kA SCCR at 400 V and 690 V is the same across the board, so you don't lose headroom on higher-voltage lines. The 97 mm depth and 45 mm width fit the S00 footprint, which is the smallest SIRIUS frame — useful when panel space is tight.
Panel integration
Any mounting position allowed. Screw-type terminals for the main current circuit accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². The screwdriver shaft diameter is 5 to 6 mm, Pozidriv size 2 tip. Clearance: 50 mm upwards and downwards, 30 mm to the side, 0 mm forwards and backwards — so you can butt it against the backplane and adjacent devices with minimal gap.