Siemens 3RV2011-1AA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1AA10 SIRIUS Motor Protection Circuit Breake

MPN3RV2011-1AA10
Active

Siemens SIRIUS 3RV2011-1AA10 motor protection circuit breaker, Class 10, 100 kA SCCR at 400 V, screw-type terminals, 45 mm width.

$82.99 – $187.66Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2011-1AA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2011-1AA10 — Electrical
ParameterValue
Rated operational current (Ie)1.6 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2011-1AA10 — Protection & Tripping
ParameterValue
Overload release setting range1.1 ... 1.6 A
Instantaneous short-circuit trip current21 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2011-1AA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2011-1AA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2011-1AA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2011-1AA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2011-1AA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

It is Class 10 trip, detects phase failure, and has no ground-fault detection.

Short-circuit ratings and selectivity

That kind of SCCR headroom means you can usually coordinate it downstream of a larger molded-case or air circuit breaker without worrying about the motor starter becoming the weak link in a fault.

Width is 45 mm, depth 97 mm, height 97 mm.

Terminals and wiring

Main circuit connections are screw-type terminals sized for M3 screws. Accepts up to 2x 4 mm² solid or stranded, or 2x (0.75 to 2.5 mm²) — plenty for the motor leads on a fractional-to-small integral-horsepower motor. No special torque specs in the evidence, but standard M3 screw torque around 0.5–0.6 Nm will get you a reliable connection. The screw terminals are a plus for panel builders who prefer them over spring-clamp for high-vibration environments.

Frequently asked questions

What clearance is needed around the 3RV2011-1AA10 in a panel?

50 mm above and below, 30 mm to the sides, zero clearance in front or back. Mounting position is any orientation.

Does this breaker detect phase failure?

Yes, phase failure detection is included. Ground fault detection is not available on this model.

MPN
3RV2011-1AA10