Siemens 3RV2011-1AA25-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1AA25-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV2011-1AA25-ZX95
Active

Siemens SIRIUS 3RV2011-1AA25-ZX95, motor protection circuit breaker, Class 10, 100 kA breaking capacity at 400 V, screw and snap-on mounting onto 35 mm DIN rail, spring-loaded terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-1AA25-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2011-1AA25-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)1.6 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV2011-1AA25-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range1.1 ... 1.6 A
Instantaneous short-circuit trip current21 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2011-1AA25-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2011-1AA25-ZX95 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²)

Mechanical

3RV2011-1AA25-ZX95 — Mechanical
ParameterValue
Height106 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2011-1AA25-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2011-1AA25-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV2011-1AA25-ZX95 is a motor protection circuit breaker, designed specifically for protecting motor circuits against overloads and short circuits. It mounts onto a standard 35 mm DIN rail per DIN EN 60715, using either screws or a snap-on mechanism, making it a direct fit for most European-style control panels. Its Class 10 trip characteristic means it will disconnect within 10 seconds at 7.2x the thermal setting, which is the standard for standard-duty induction motors — pumps, fans, and compressors that don't need an ultra-fast trip. The 100 kA breaking capacity at 400 V and 690 V gives it the headroom to sit upstream of a motor starter without needing a separate backup fuse, simplifying the panel layout. Phase failure detection is built in, so it will drop the load if one line drops out — a common cause of single-phasing motor burnouts. The spring-loaded terminals on the main circuit accept 2x (0.5...2.5 mm²) solid or stranded wire, which is the standard range for control wiring in this class.

Mounting and Clearances

At 45 mm wide and 97 mm deep, it occupies a single 45 mm slot on the DIN rail. The mounting position is any orientation, which helps when laying out a dense panel. Required clearances: 50 mm above and below, 30 mm to the side, and 0 mm forward/backward — meaning it can be packed tight against the back panel or enclosure door.

Auxiliary Contact Ratings

The auxiliary contact block handles 1 A at 24 V, 0.5 A at 120/125/230 V, and 0.15 A at 60 V. These are the standard signal-level ratings for feeding a PLC input or a contactor coil — not for power switching.

Frequently asked questions

What is the breaking capacity of this circuit breaker?

It has a 100 kA breaking capacity at 400 V and also at 690 V, which is a high-interrupting rating suitable for most industrial distribution panels without requiring upstream current-limiting fuses.

How do I get current pricing and availability for 3RV2011-1AA25-ZX95?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to get current pricing and availability confirmed at quote time.

What are the mounting dimensions for this part?

Width is 45 mm, depth is 97 mm, and height is 106 mm. It mounts on 35 mm DIN rail per DIN EN 60715, with required clearances of 50 mm above and below, and 30 mm to the sides.

MPN
3RV2011-1AA25-ZX95