Motor protection circuit breaker, SIRIUS, 2 A, CLASS 10
Rated operational current is 2 A, with a magnetic short-circuit release set at 26 A. The breaker handles fault currents up to 100 kA at 240 V, 400 V, and 500 V AC, and 10 kA at 690 V AC — sufficient for most industrial panel SCCR requirements when coordinated with upstream fuses or a main breaker. Termination is via spring-type terminals, which accept solid or stranded copper up to 4 mm² per conductor. The breaker ships with factory-installed transverse auxiliary switches: 1 NO + 1 NC contact for remote status indication or interlocking.
Side-by-side mounting is permitted with zero clearance — no derating required for adjacent units at the rated current.