Skip to main content
Siemens 3RV2011-1DA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1DA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV2011-1DA10-ZX95
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2011-1DA10-ZX95, CLASS 10 trip class, 100 kA SCCR at 400 V, 97 x 45 x 97 mm, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-1DA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2011-1DA10-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)3.2 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV2011-1DA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range2.2 ... 3.2 A
Instantaneous short-circuit trip current42 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2011-1DA10-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2011-1DA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12

Mechanical

3RV2011-1DA10-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2011-1DA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2011-1DA10-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor protection circuit breaker, CLASS 10, 100 kA SCCR

The Siemens SIRIUS 3RV2011-1DA10-ZX95 is a motor protection circuit breaker designed for direct motor starting and protection. It carries a CLASS 10 trip class, meaning it will trip within 10 seconds at 7.2× the thermal setting — fast enough to protect standard induction motors during a locked-rotor event without nuisance tripping on normal starts. Rated short-circuit breaking capacity hits 100 kA at 400 V, which covers most industrial distribution panels without needing upstream fuses for current-limiting coordination. At 690 V it still holds 10 kA, enough for IT systems or older 600 V class plants. Mounts via screw or snap-on onto 35 mm DIN rail per EN 60715. Panel cutout is 45 mm wide, 97 mm tall, and the body depth is 97 mm — standard for the SIRIUS 3RV2 frame. Any mounting position allowed, so it fits tight enclosures or horizontal bus layouts.

Clearance and integration

Minimum clearances to adjacent components: 50 mm upwards, 50 mm downwards, 30 mm to the side. Zero clearance required forwards or backwards — the breaker can be mounted flush against a panel backplate or enclosure wall. Ambient operating range -20 to +60 °C with temperature compensation active across the same span. Storage and transport range -50 to +80 °C. The breaker derates above 40 °C per the thermal curve; the compensation keeps the trip curve accurate across the operating band.

Frequently asked questions

Where can I buy 3RV2011-1DA10-ZX95 and get a price?

Sourced through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, no stock or price figures held on this listing.

What are the key ratings for 3RV2011-1DA10-ZX95?

CLASS 10 trip class, 100 kA SCCR at 400 V, rated voltage 20–690 V AC, motor protection design with phase failure detection, screw-type terminals accepting 2x 0.75–2.5 mm² or 1x 4 mm², dimensions 97 x 45 x 97 mm, snap-on or screw mount on 35 mm DIN rail.

Will 3RV2011-1DA10-ZX95 drop into a panel specified around 3RV2011-0AA10?

The 3RV2011-1DA10-ZX95 shares the same 45 mm width and 97 mm height as the 3RV2011-0AA10 frame, and both mount on 35 mm DIN rail per EN 60715. Terminal layout and screw-type connections are identical. It should fit the same panel cutout and rail position without rewiring, but verify the trip setting range and SCCR rating on the nameplate against your BOM — the -ZX95 suffix may carry a different factory-set current range or special version marking.

MPN
3RV2011-1DA10-ZX95