Skip to main content
Siemens 3RV2011-1EA20-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1EA20-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV2011-1EA20-ZW97
Active

Siemens SIRIUS 3RV2011-1EA20-ZW97 motor protection circuit breaker, CLASS 10 trip class, 100 kA breaking capacity at 400 V, 4 A rated current at 480 V, screw and snap-on DIN rail mounting, spring-loaded terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-1EA20-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2011-1EA20-ZW97 — Electrical
ParameterValue
Rated operational current (Ie)4 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV2011-1EA20-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range2.8 ... 4 A
Instantaneous short-circuit trip current52 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2011-1EA20-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2011-1EA20-ZW97 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (20 ... 12)

Mechanical

3RV2011-1EA20-ZW97 — Mechanical
ParameterValue
Height106 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2011-1EA20-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2011-1EA20-ZW97 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

What it is and what it does

The Siemens 3RV2011-1EA20-ZW97 is a SIRIUS-brand motor protection circuit breaker designed for motor protection, with phase failure detection built in. It covers a rated voltage range of 20 to 690 V, with a CLASS 10 trip class — meaning it will trip within 10 seconds under locked-rotor conditions, matching the thermal curve of standard induction motors. Breaking capacity hits 100 kA at 400 V and 500 V, and 100 kA at 240 V — so it can safely interrupt a fault up to that level without cascading upstream, which simplifies coordination in a panel. Rated current at 480 V is 4 A, and at 600 V it's also 4 A; the fuse backup ratings are gL/gG 32 A at 400 V and 500 V, and gL/gG 25 A at 690 V.

Panel fit and mounting

Mounts via screw and snap-on onto 35 mm standard mounting rail per DIN EN 60715, in any mounting position — so it drops into a standard DIN-rail enclosure without special brackets. Dimensions: 97 mm deep, 45 mm wide, 106 mm high. Clearance requirements: 50 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards — that backwards zero means it can sit flush against a backplate, handy when you're packing a tight gland plate. Main circuit connections use spring-loaded terminals, accepting 2x (0.5 to 4 mm²) solid or stranded wire — no screwdriver torque needed, just strip and push.

Environmental and duty limits

Operates from -20 to +60 °C, with temperature compensation active across that same range. Storage and transport range is -50 to +80 °C. Maximum switching frequency in AC-3 duty is 15 operations per hour — fine for a conveyor or pump start, not for a rapid-cycling application. Horsepower ratings: 0.33 hp at 230 V, 0.13 hp at 110/120 V, 0.8 hp at 200/208 V, 0.75 hp at 220/230 V, 2 hp at 460/480 V, and 3 hp at 575/600 V.

MPN
3RV2011-1EA20-ZW97