It is part of the SIRIUS series, a modular family of industrial control gear. The breaker offers a breaking capacity of 100 kA at 400 V and 500 V, and 4 kA at 690 V. At 240 V it also holds 100 kA.
Width is 45 mm (one standard modular unit), depth 97 mm, height 97 mm. Required clearances: 50 mm above and below the device, 30 mm to the side, zero forward or backward. These are the minimums for arc flash containment and thermal dissipation — a panel builder should respect them, especially when ganging multiple breakers. Terminals are screw-type for the main current circuit, accepting 2×(0.75–2.5 mm²) solid or stranded, or 2×4 mm². The main contact screws are M3. This is standard for panel wiring up to the breaker's rated current.
Lifecycle stage is current; no end-of-life notice on record. The supply channel is standard for SIRIUS components: sourced on request, with pricing and lead time confirmed at quote time.