Skip to main content
Siemens 3RV2011-1FA25-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1FA25-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV2011-1FA25-ZX95
Active

Siemens SIRIUS 3RV2011-1FA25-ZX95, motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 3.5...5 A, magnetic short-circuit release 65 A, spring-type terminals, 1 NO + 1 NC auxiliary contacts, 100 kA breaking capacity at 400 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-1FA25-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker

Electrical

3RV2011-1FA25-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)5 A
Rated voltage20 ... 690 V

Protection & Tripping

3RV2011-1FA25-ZX95 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current65 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA

Specifications

3RV2011-1FA25-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Other specifications

3RV2011-1FA25-ZX95 — Other specifications
ParameterValue
At 400 V rated value100 kA
At 500 V rated value100 kA
Substance prohibitance10/01/2009

Product details

The Siemens SIRIUS 3RV2011-1FA25-ZX95 is a motor protection circuit breaker in the S00 frame size, designed to combine overload and short-circuit protection in a single device for a 3-phase motor branch. Its CLASS 10 trip characteristic means it will trip within 10 seconds at 7.2× the overload setting — fast enough to protect standard induction motors during a locked-rotor event without nuisance tripping on normal starts. The adjustable overload release covers 3.5 to 5 A, and the fixed magnetic short-circuit release fires at 65 A, so it clears a hard fault before the motor contributes significant let-through energy. Breaking capacity hits 100 kA at 240 V, 400 V, and 500 V AC, then drops to 4 kA at 690 V AC — the high 100 kA figure means it can be used downstream of a high-capacity transformer without requiring a current-limiting upstream breaker in most industrial panels. The spring-type terminals accept 2× (0.5 to 1.5 mm²) solid or ferruled stranded, and the S00 width of 45 mm lets it snap onto a 35 mm DIN rail per EN 60715, with zero side clearance needed for side-by-side mounting.

Sourcing and fit verification

This exact order code is sourced through independent distribution channels and quoted to order against an RFQ — availability and current pricing are confirmed at quote time. The 45 mm width and 97 mm depth match the standard S00 footprint, so it drops into any panel already laid out for a SIRIUS motor starter without re-drilling the DIN rail or re-routing the main conductors.

Frequently asked questions

Will the 3RV2011-1FA25-ZX95 fit in a panel designed for the 3RV2021-1FA15?

Yes — both are 45 mm wide and mount on 35 mm DIN rail. The S00 frame of this breaker is 97 mm deep versus the S0 frame's 97 mm depth, but the S00 is shorter in overall height (97 mm vs 97 mm, but the S0 has a taller body). The spring terminals on this variant may require different wiring preparation compared to the screw terminals on the 3RV2021-1FA15.

MPN
3RV2011-1FA25-ZX95