At 690 V it holds 4 kA. Trip Class 10 means it disconnects within 10 seconds under locked-rotor conditions, matching standard induction motor thermal curves.
Dimensions: 97 mm depth, 45 mm width, 97 mm height. Requires 50 mm clearance upwards and downwards, 30 mm at the sides, and zero forwards or backwards — tight on the rail but needs breathing room for heat dissipation and wiring access. Screw-type terminals for the main circuit accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². Main contact screw size is M3.
Current production stage — the 3RV2011-1GA10-ZX95 is in active manufacture.