Siemens 3RV2011-1GA25-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1GA25-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV2011-1GA25-ZW97
Active

Siemens SIRIUS 3RV2011-1GA25-ZW97, motor protection circuit breaker, 6.3 A at 480/600 V, 100 kA SCCR at 400 V, Trip Class 10, screw and snap-on mounting onto 35 mm DIN rail, spring-loaded terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2011-1GA25-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2011-1GA25-ZW97 — Electrical
ParameterValue
Rated operational current (Ie)6.3 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV2011-1GA25-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range4.5 ... 6.3 A
Instantaneous short-circuit trip current82 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2011-1GA25-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2011-1GA25-ZW97 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²)

Mechanical

3RV2011-1GA25-ZW97 — Mechanical
ParameterValue
Height106 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2011-1GA25-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2011-1GA25-ZW97 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor Protection Circuit Breaker — SIRIUS 3RV2011-1GA25-ZW97

The Siemens SIRIUS 3RV2011-1GA25-ZW97 is a motor protection circuit breaker designed for protecting three-phase induction motors against overload and short-circuit. It is part of the SIRIUS family, the standard modular component system for motor feeders in industrial control panels. This variant carries a continuous current rating of 6.3 A at 480 V and 600 V, and delivers a short-circuit breaking capacity of 100 kA at both 240 V and 400 V — sufficient for high-fault installations like large MCCs or distribution boards. Trip Class 10 means it will trip within 10 seconds at 7.2× the thermal setting current, matching the standard thermal withstand curve of standard IEC induction motors. Phase failure detection is built in, so a lost phase on the supply side will cause the breaker to open before the motor single-phases to destruction.

Mounting and Wiring

Mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715. Any mounting position is acceptable — no derating for horizontal or vertical orientation. The spring-loaded terminals (cage clamp) accept 2× 0.5…2.5 mm² solid or stranded conductors, saving wire-prep time compared to screw terminals. Dimensions are 45 mm wide × 106 mm high × 97 mm deep. The 45 mm width occupies two standard module spaces on the DIN rail.

Breaking Capacity and Coordination

Rated short-circuit breaking capacity is 100 kA at 400 V, dropping to 4 kA at 690 V. For gL/gG fuse backup at higher voltages, the maximum permitted fuse rating is 50 A at 400 V, 40 A at 500 V, and 35 A at 690 V. This allows Type 2 coordination with a standard fuse upstream.

Frequently asked questions

Will 3RV2011-1GA25-ZW97 fit a panel designed for 3RV2021-1GA25?

Yes, it drops in without rewiring. Both parts share the same 45 mm width, 35 mm DIN rail snap-on mounting, and same terminal spacing. The only difference is terminal type: spring-loaded on the -ZW97 vs screw on the 3RV2021-1GA25. If the panel wiring uses ferruled conductors, the spring terminals accept them directly.