Rated for 20 to 690 V AC, it delivers a 100 kA breaking capacity at 400 V, 500 V, and 690 V, so it can safely interrupt high-fault currents in industrial distribution panels without upstream fuses or larger breakers. At 230 V it is rated for 0.2 kW motor loads; at 575/600 V it covers 0.5 hp. Ground fault detection is not included, so a separate ground-fault relay is needed if that protection is required.
Main circuit terminals are M4 screw-type, accepting 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded wire. The 50 mm clearance above and below the unit (no side clearance needed) simplifies wiring in dense panels.