Skip to main content
Siemens 3RV2021-0JA20-0BA0 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2021-0JA20-0BA0 SIRIUS Motor Protection Circuit B

MPN3RV2021-0JA20-0BA0
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2021-0JA20-0BA0, size S0, 1 A at AC-3 400 V, Trip Class 10, 100 kA breaking capacity, screw and snap-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2021-0JA20-0BA0 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0
3RV2021-0JA20-0BA0 — Electrical
ParameterValue
Rated operational current (Ie)1 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2021-0JA20-0BA0 — Protection & Tripping
ParameterValue
Overload release setting range0.7 ... 1 A
Instantaneous short-circuit trip current13 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2021-0JA20-0BA0 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)500
Endurance, auxiliary contacts (typ.)500
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2021-0JA20-0BA0 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 10 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 6 mm²)
3RV2021-0JA20-0BA0 — Mechanical
ParameterValue
Height119 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2021-0JA20-0BA0 — Environmental
ParameterValue
Operating temperature-50 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2021-0JA20-0BA0 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor protection circuit breaker, 1 A, Class 10 — panel fit and ratings

The Siemens 3RV2021-0JA20-0BA0 is a SIRIUS motor protection circuit breaker in size S0, rated 1 A at AC-3 400 V with Trip Class 10, designed to protect motor feeders in control panels. It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, in any orientation, with 45 mm width and 97 mm depth — fits standard S0 slot in a panel layout. Breaking capacity holds at 100 kA across 240 V, 400 V, 500 V, and 690 V AC — that means it can interrupt a bolted fault up to that level without upstream coordination failure, which simplifies SCCR compliance in a branch circuit.

Integration — DIN rail, spring-loaded terminals, clearances

Spring-loaded terminals on the main current circuit accept 2x 1–10 mm² solid or stranded conductors; screwdriver shaft diameter 3 mm, tip 3.0 x 0.5 mm for the terminal screws. Required clearances: 50 mm upwards and downwards, 30 mm at the sides, 0 mm forwards and backwards — tight panel spacing is workable.

MPN
3RV2021-0JA20-0BA0